KPF type self-locking manual balance regulating valve

KPF manual self-locking balance regulating valve integrates flow regulation and quantification functions, effectively solving uneven temperature distribution in heating/air conditioning systems. Equipped with an opening indicator, locking device, and pressure measuring valve, it can be debugged and locked once using a special intelligent instrument when installed at each branch and user entrance, controlling total system water volume and eliminating the "large flow, small temperature difference" issue. Suitable for both supply and return pipes (preferably return pipes for high-temperature loops), it eliminates the need for additional shut-off valves.

一.Product Introduction
KPF type manual self-locking balance regulating valve: It is a kind of valve with special functions. In addition to the function of regulating valve, it can also realize flow quantification, which can effectively solve the problem of uneven room temperature and heat in the heating (air conditioning) system.Since the valve is equipped with an opening indicator, an opening locking device and a small pressure measuring valve for flow measurement, as long as a balance valve of appropriate size is installed at each branch and the user entrance, and a special intelligent instrument is used for one-time debugging and locking, the total water volume of the system is controlled within a reasonable range, and the unreasonable phenomenon of “large flow and small temperature difference” can be overcome. It is an ideal product in the heating system.

Manual self-locking balance regulating valve can be installed on the water supply pipe, it can also be installed on the return pipe, generally installed on the return pipe, especially for high temperature loops, in order to facilitate debugging, it should be installed on the return pipe road, the water supply and return pipe with the balance valve installed does not need to be equipped with a shut-off valve.
二.Product Features
1.Functions: lt has the function of a regulating valve and can achieve quantitative flow, effectively solving theuneven room temperature problem in heating (air conditioning) systems.

2.Configurations: Equipped with an opening degree indicator, an opening degree locking device, and a smallpressure measuring valve for flow measurement.

3.Commissioning and Role: install appropriate scale balance valves on each branch and user inlet, lock themafter one – time debugging with a dedicated intelligent instrument to control the total water volume of thesystem within a reasonable range, and overcome the unreasonable phenomenon of “large flow and smalltemperature difference”.

4.Installation Position: Can be installed on the supply pipe or return pipe. Generally, it is installed on the returnpipe. Especially for high – temperature loops, for convenient debugging, it should be installed on the return pipe.

5.Matching: The supply and return pipes with a balance valve installed do not need to be equipped with a stop valve.
三.Technical data

Model number PN Working pressure/MPa Applicable temperature /℃ Applicable media Transmission method
KPF-10 10 1.0 -29~350 Water, steam Transmission method manual, gear transmission, electric
KPF-16 16 1.6
KPF-25 25 2.5

 

Model number Material
Valve body, valve cover, packing gland, handwheel Valve stem, valve disc sealing ring Indicator plate, stem nut, nut sleeve
KPF-10 Gray cast iron, (cast steel) Stainless steel Brass
KPF-16
KPF-25

四.The main shape and connection size

DN L H H1 D0
15 130 150 160 80
20 150 160 170 180
25 160 182 197 80
32 180 192 207 90
40 200 250 270 100
50 230 264 284 120
65 290 380 410 200
80 310 413 448 200
100 350 446 506 240
125 400 540 595 240
150 480 623 688 360
200 495 687 762 400
250 622 782 867 500
300 698 914 1009 500
350 787 968 1073 680
400 914 1037 1152 680
500 978 1440 1440
600 1295 1790 1790